The brown and blue wires must be connected, or F1 must be set to “1” using the remote control.
The harness is reversed; the short harness plugs into the IXIO.
The RECORD control uses a normally closed safety circuit; set the safety output to N.C.
The IXIO is defaulted to monitoring ON; connect the two (2) purple monitoring wires to the control.
Verify the pattern width shutters are not closed (the software should still be set to wide).Verify the active infrared safety pattern is not tilted out too far away from the door.
Turn off the 2nd active infrared safety pattern row.
If the red LED illuminates, the active infrared safety curtain needs adjusted.
If the green LED illuminates, the microwave activation angle/sensitivity/immunity needs adjusted.
The two (2) purple wires are for monitoring and the yellow wire is for N.C. activation relay.
Double-click the gray knob to turn on the visible red aligment spots or press UNLOCK > MAGIC WAND > + on the remote control, and then use the red knob to adjust active infrared saftey pattern to within 3” of the face of the sliding door panel. After adjustment, relaunch a setup.
If the door is equipped with a two-way traffic option, connect the white and green wires to the activation circuit.
If the door is NOT equipped with a two-way traffic option, DO NOT connect the white and green wires to the activation circuit; instead, connect the brown and blue wires to the safety circuit.
Using the LCD, set RAD: REENTRY to value “”3″” or “”4″”. Walk-test to ensure there is a minimum of a 24” reactivation zone.
A lock code has been entered. To remove it, power cycle the IXIO and then press UNLOCK > LOCK > 0000.